Connecting Data and Supply Cables
Rexroth IndraControl S67 Digital Module 8 Outputs – 2.0 A (4×M12)
Connection
Contact
1
1
2
3
4
2
4
3
Tab. 6-3:
Supply cable ready-made on one end: Contact assignment
Fig. 6-2:
Supply cable ready-made on one end
NOTICE
Observe the maximum current carrying capacity per supply line (U
well as the total current consumption for all IndraControl S67 components.
Both values must not exceed 4 A, as an increase in current causes the con‐
tacts to overheat and damages the IndraControl S67 components.
To connect the supply cable to the field bus coupler and to the modules, pro‐
ceed as follows:
1. Disconnect the power supply from those devices the S67-DO8-M12-2A
module is mounted to.
2. For example, if one I/O module and the S67-DO8-M12-2A module are
connected to the field bus coupler, connect the cable K1 with the associ‐
ate IN and OUT connections to the I/O module for the supply voltage
transmission as shown in the following figure.
3. For the S67-DO8-M12-2A module, feed in the supply voltages again us‐
ing the two IN connections (K2, K3) as shown in the following figure.
4. Tighten the plugs and sockets using the knurled-head screws.
5. Screw a protective cap on all unused connections to comply with the de‐
gree of protection IP 67.
For information on the supply voltage cable connection (K0) to the IN input
(6) of a field bus coupler, refer to the corresponding application descriptions
of the field bus couplers.