DOK-CONTRL-S67DO8M122A-AP03-EN-P
Rexroth IndraControl S67 Digital Module 8 Outputs – 2.0 A (4×M12)
4.9.3

Communication

4.9.4

Digital Outputs

4.9.5

Actuator Selection Specifications

Supply voltage
Logic and sensor voltage U
LS
Actuator voltage U
A
Supply current
Logic and sensor current I
LS
Actuator current I
A
Protection function
Derating has to be complied with
Tab. 4-6:
Module supply
S-BUS connection
Tab. 4-7:
Communication
Number of outputs
Connection type
Termination technique
Output voltage
Output current (per channel)
Voltage drop against U
at 2.0 A
A
Output current (module)
Leakage current when switched off
Output circuit
Tab. 4-8:
Digital outputs
Delay time HW
From 0 to 1 (0 – 90 %)
From 1 to 0 (0 – 90 %)
Rise time
From 0 to 1
Drop-out time
From 1 to 0
Cable length, unshielded
Strength against reverse voltages
Load type
Bosch Rexroth AG
Device Description
24 V DC (-25 % ... +30 %)
24 V DC (-25 % ... +30 %)
Typically 45 mA (logic component only)
Typically 55 mA + actuator
Reverse polarity protection for U
Shielded M12 male connector,
B-coded, 5-pin
8
M12 male connector, A-coded, 5-pin
2- to 3-wire
≤ U
A
2.0 A (max. 2.4 A),
Short-circuit/overload proof (thermal
shutdown)
Maximum 0.2 V DC
Maximum 8 A
Typically 780 µA
High-side switching
Typically 75 µs (ohmic load)
Typically 265 µs (ohmic load)
Typically 30 µs (ohmic load)
Typically 50 µs (ohmic load)
≤ 30 m
≤ 2 A
Inductive, ohmic loads and lamps
19/69
+ U
LS
A

Advertisement