ID2000 Series Operating Manual
PANEL STATUS: PRE-ALARM
This condition is when one or more input devices has
signalled a PRE-ALARM to the panel - i.e. a reading which
is higher than normal but not yet at the FIRE level.
This condition continues to be shown until superseded
by a higher-priority condition (i.e. FIRE) or until cleared
by pressing the RESET pushbutton.
The occurrence may have been 'accepted' at the panel
by pressing the ACCEPT pushbutton, if so the status is
still 'PRE-ALARM'.
The panel indications and external equipment are as follows:
LAMP indications:
POWER (green):
PRE-ALARM LAMP (amber):
All other LAMPs:
The LCD displays the message shown below:
Status: PRE-ALARM
(location) (device type)
For approximately two minutes after a Pre-Alarm is
accepted, line 2 shows a scrollable message (use
and
to scroll) giving full details about the occurrence:
'PRE-ALARM' (Device number) (zone) (type)
(analogue value at time of alarm) (location) (date &
time of alarm) plus indication as to whether any further
alarms exist, indicated by 'MORE: PRESS
Internal buzzers:
if not accepted:
Pre-alarm buzzer (high-pitched):
if accepted or buzzer silenced:
Pre-alarm buzzer muted:
Circuits Controlled Internally: and
External Devices: Programmed function.
A1 - 5
ON
if not accepted: FLASHING
if accepted:
STEADY
OFF
(date)
(time)
or
ON STEADY
Intermittent - one
0.5 sec pulse ON
every 2 minutes
997-434-000-4, Issue 4