Outputs - Honeywell NOTIFIER ID2000 Series Operating Manual

Hide thumbs Also See for NOTIFIER ID2000 Series:
Table of Contents

Advertisement

ID2000 Series Operating Manual
For some Network systems (dependent on configuration),
there may be a facility, available at the Master Panel only,
to perform a disablement or enablement on a complete
zone at a different panel on the network. If this feature is
available, the procedure is as follows:
1 At the Master Panel, when you enter the DISABLE/
ENABLEMENT procedure and select the ENTIRE
ZONE option the question shown below is displayed:
DISABLED:SLAVE no. (0=MASTER):n
2 The suggested value under the cursor is the number
of the local panel. If you enter a different value - i.e.
you select a panel other than the local one - the
question shown below is displayed. Enter the required
zone number remembering that it refers to the Slave
panel.
Remote DISABLE at Slave n:
Enter Zone no.:
3 The system then displays the options shown below:
0=Enable/1=Disable:
Press 0 or 1 as required. Unlike when disabling local
zones, there is no option to specify whether sensors,
all inputs, or input and outputs, are to be included.
That is determined by the configuration of the Slave
panel which you have selected.
Note: This facility can be initiated only at the Master
panel, unlike the REMOTE TEST facility described
in Section 4.8.1, which can be initiated at any
panel on the network.

4.9.3 Outputs

To disable or enable outputs:
1 From the Top Level display, press pushbutton '1'. The
DISABLE/ENABLEMENT menu is displayed:
DISABLE/ENABLEMENT: 0=Individual/
1=Entire Zone/2=Outputs:
2 Press the '2' pushbutton. The following is displayed:
DISABLE/ENABLEMENT: 0=Sounders/
1=Control Outputs/2=Remote Fire O/P:
3 Press the pushbutton that corresponds with the
required option. The following is displayed:
0=Enable/1=Disable:
4 Depending upon your selection, one of the following
is displayed ('panel' is not required for TX circuits):
ENABLE (type), (panel)
Confirm (
DISABLE (type), (panel)
Confirm (
5 Press
27
/X)?
! ! ! ! !
/X)?
! ! ! ! !
or
as required.
997-434-000-4, Issue 4
May 2010

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents