4.10.4 Delays - User Option

[U0 Disable/Enable]
4
Disable Delays
Press
5
[U0 Disable/Enable]
FIRE
DISABLEMENT
TEST
DELAYS ACTIVE
FIRE OUTPUT: FAULT / DISABLED
FIRE OUTPUT ACTIVE
PLANT ALARM
POWER
The Disable / Enable Delays option allows the user to
cancel or initiate the Delays function of the panel, which
is configured during commissioning (refer to 997-457-
000-X
ID61/62
Series
Commissioning and Configuration Manual,
Sections 5.5.5.4 Primary/Extend Delay Timer and 5.7.8
CBE Zones).
To Disable/Enable Delays:
1 Using the numeric keypad, press the '
select the Disable/Enable Delays option:
1:Zone
3:Day Mode
4:Delays
2 At the prompt, press the '
Delays operation. If delays are disabled, the LCD
prompts to enable delays, and vice versa.
to confirm
When the delays are disabled, the DELAY ACTIVE
LED is extinguished. When the delays are enabled,
the LED is illuminated.
1:Zone
3:Day Mode
4:Delays
If a Day Mode time period is configured, the CBE Rule
delays will activate when Day Mode is started either:
a. Using the Disable/Enable menu, or
b. When Digital/ÜE Input 1 is operated (if this input is
configured during commissioning for Day Mode
Start).
These delays will be deactivated when Day Mode is
ended, either automatically at the end of the configured
Day Mode period, or by one of the following:
a. Using the Disable/Enable menu,
b. When the Digital/ÜE Input 1 is operated,
c. Delays are disabled using the Disable/Enable menu.
33
Panel
Installation,
' button to
4
2:Outputs
' button to confirm the
5
<:Cancel
2:Outputs
997-458-000-8, Issue 8