Viessmann Vitocal 200-G Series Installation And Service Instructions Manual page 94

Heat pump with electric drive
Table of Contents

Advertisement

Specification
Specification for water/water heat pumps
230 V appliances
Type BWC-M in conjunction with "conversion kit for wa-
ter/water heat pump"
Heating performance data to EN 14511
(W10/W35, 5 K spread)
Rated heating output
Cooling capacity
Power consumption
Coefficient of performance
Brine (primary intermediate circuit)
Capacity
Minimum flow rate
Residual head at minimum flow rate
Max. flow temperature (brine inlet)
Min. flow temperature (brine inlet)
Heating water (secondary circuit)
Capacity
Minimum flow rate
Residual head at minimum flow rate
Max. flow temperature
Note
Further specifications: See "Specification for brine/
water heat pumps".
94
kW
kW
kW
(COP)
ε
l
l/h
mbar
kPa
°C
°C
l
l/h
mbar
kPa
°C
(cont.)
201.B06
7.62
6.48
1.36
5.61
3.3
1600
535
53.5
25
7.5
3.3
660
608
60.8
65
201.B08
201.B10
9.95
13.44
8.60
11.66
1.64
2.27
6.07
5.92
3.3
3.8
2130
2890
295
770
29.5
77.0
25
25
7.5
7.5
3.5
3.8
860
1160
675
625
67.5
62.5
65
65