Viessmann Vitocal 200-G Series Installation And Service Instructions Manual page 79

Heat pump with electric drive
Table of Contents

Advertisement

Control parameter report
External heat generator
Parameter
"Enable external heat source"
"Priority ext. heat source/instant. heating
water heater"
"Dual mode temperature external heat
source"
"Start threshold external heat source"
"Start delay external heat source"
"Min. flow temperature mixer external
heat source ON"
"Min. runtime external heat source"
"Run-on time external heat source"
"Max. excess flow temp external heat
source"
"Enable external heat gen. for central
heating"
"Enable external heat source for DHW
heating"
"Dual mode heat pump operation"
"Shutdown limit, heat pump dual mode"
"Enable min. temp. maintenance for ext.
HS"
"Enable boiler water temperature sen-
sor"
DHW
Parameter
Set DHW temperature
Min. DHW temperature
Max. DHW temperature
Hysteresis DHW temperature heat pump
Hysteresis DHW temperature booster heat-
er
Start optimisation for DHW heating
Stop optimisation for DHW heating
Set DHW temperature 2
Temperature rise per hour for DHW heating
Temperature sensor at bottom of DHW cyl-
inder
Max. runtime DHW heating in heating mode 6011
Max. interruption of DHW heating for central
heating
Enable booster heaters for DHW heating
Enable electric heaters for DHW heating
Priority DHW heating with combi cylinder
Start attempts for DHW after high pressure
shutdown
(cont.)
Code
Delivered condition Commission-
7B00
0
7B01
1
7B02
100 (
7B03
300 (
7B04
30 min
7B05
0
7B06
20 min
7B07
10 min
7B0B
0
7B0C
1
7B0D
0
7B0E
1
7B0F
500 (
7B10
0
7B11
1
Code
Delivered condition Commission-
6000
500 (
6005
100 (
6006
600 (
6007
50 (
6008
100 (
6009
0
600A
0
600C
600 (
600D
30 K/h
600E
0
240 min
6012
90 min
6014
0
6015
0
6016
0
6017
0
Commissioning/service reports
ing
10 °C)
30 min)
≙ –
50 °C)
ing
50 °C)
10 °C)
60 °C)
5 K)
10 K)
60 °C)
Maintenance/
service
Maintenance/
service
79