Viessmann Vitocal 200-G Series Installation And Service Instructions Manual page 34

Heat pump with electric drive
Table of Contents

Advertisement

Installation sequence
Electrical connection
Plug
sXG
Terminals
Function
225.1
Heating circuit pump of the heating
circuit with mixer M2/HC2
M2
r
225.2
Mixer motor control, heating circuit
M2/HC2
M2
Mixer CLOSE signal
225.3
Mixer motor control, heating circuit
M2/HC2
M2
Mixer OPEN signal
Luster terminals (message and safety connections)
Set the required parameters during commissioning:
See page 55 onwards.
Terminals
Function
F1
Fuse 6.3 A (slow)
X1
Earth conductor X1.
X2
Neutral conductor X2.N
X3.1
Switched phase
34
(cont.)
?
Explanation
Connect a temperature limiter in series to restrict the
maximum temperature of underfloor heating circuit (if
installed).
Note
In systems without heating water buffer cylinder the
temperature limiter is connected to X3.2/X3.14 at the
luster terminals: See chapter "Temperature limiter to re-
strict the maximum temperature of underfloor heating
circuit".
Connection values:
Output: 100 W
Voltage: 230 V~
Max. switching current: 4(2) A
Connection values:
Output: 10 W
Voltage: 230 V~
Max. switching current: 0.2(0.1) A
Connection values:
Output: 10 W
Voltage: 230 V~
Max. switching current: 0.2(0.1) A
Explanation
Note
Observe the total load 1000 W of all connected compo-
nents.
Terminals for earth conductors of all associated system
components
Terminals for neutral conductors of all associated sys-
tem components
Via control unit ON/OFF switch
Note
Observe the total load 1000 W of all connected compo-
nents.