Viessmann Vitocal 200-G Series Installation And Service Instructions Manual page 19

Heat pump with electric drive
Table of Contents

Advertisement

Hydraulic connections
Fitting the primary/secondary circuit connection set (standard delivery)
E
D
+
1.
Fig. 11
Primary circuit flow (heat pump brine inlet), con-
A
nection Cu 28 x 1.5 mm
Primary circuit return (heat pump brine outlet),
B
connection Cu 28 x 1.5 mm
Secondary circuit flow (DHW cylinder), connection
C
Cu 28 x 1.5 mm
Connecting the primary circuit
!
Please note
The heat transfer medium can cause corrosion
damage to on-site lines and components.
The components and lines used must be resist-
ant to the heat transfer medium. Never use zinc-
plated/galvanised pipes.
(cont.)
C
B
A
2.
5x
5x
Secondary circuit flow (heating circuits), connec-
D
tion Cu 28 x 1.5 mm
Secondary circuit return (heating circuits DHW cyl-
E
inder), connection Cu 28 x 1.5 mm
1. Equip the primary circuit with an expansion vessel
and safety valve, in accordance with DIN 4757.
Note
The expansion vessel must be approved to
DIN 4807. The diaphragms of the expansion ves-
sel and safety valve must be suitable for the heat
transfer medium.
The blow down and drain pipes should exit into a
container. This container must be able to hold
the maximum possible expansion volume of the
heat transfer medium.
2. Ensure adequate thermal and anti-vibration insula-
tion where pipes penetrate walls.
Installation sequence
19