Viessmann Vitocal 200-G Series Installation And Service Instructions Manual page 83

Heat pump with electric drive
Table of Contents

Advertisement

Control parameter report
Cooling
Parameter
Cooling function
Cooling circuit
Set room temperature separate cooling cir-
cuit
Min. flow temperature cooling
Influence room temperature hook-up cooling
circuit
Room temperature control cooling circuit
Ranking room temp sensor separate cooling
circuit
Hysteresis room temp cooling circuit
Enable flow temperature sensor cooling cir-
cuit
Cooling curve level
Cooling curve slope
Remote control cooling circ
Dew point monitor
Cooling integral start threshold
Ventilation: Vitovent 200-C and Vitovent 300-F
Parameter
Vitovent enable
Enable preheater bank electric
Enable reheater bank hydraulic
Enable humidity sensor
Enable CO2 sensor
Set room temperature
Flow rate reduced ventilation
Flow rate nominal ventilation
Flow rate intensive ventilation
Min. supply air temperature for bypass
CO2 value for raising the flow rate
Humidity value for raising the flow rate
Interval time frost protection ventilation
Intensive ventilation duration
Actual source room temperature
Heating circuit for blocking bypass damper
(cont.)
Code
Delivered condition Commission-
7100
0
7101
1
7102
200 (
7103
200 (
7104
0
7105
1
7106
0
7107
10 (
7109
1
7110
0 (
7111
12 (
7116
Do not adjust!
7117
1
7118
10 %
Code
Delivered condition Commission-
7D00
0
7D01
0
7D02
0
7D05
0
7D06
0
7D08
200 (
7D0A
7D0B
7D0C
7D0F
160 (
7D18
800 ppm
7D19
65 %
7D1A
15 min
7D1B
120 min
7D1D
1
7D21
7
Commissioning/service reports
ing
20 °C)
20 °C)
1 K)
0 K)
1.2)
ing
20 °C)
Vitovent 200-C:
3
75 m
/h
Vitovent 300-F:
3
120 m
/h
Vitovent 200-C:
3
115 m
/h
Vitovent 300-F:
170 m
3
/h
Vitovent 200-C:
155 m
3
/h
Vitovent 300-F:
3
215 m
/h
16 °C)
Maintenance/
service
Maintenance/
service
83