This chapter provides maintenance instructions, operational testing procedures,
troubleshooting guidelines, and information on replacement parts.
Routine Maintenance
Perform the following routine maintenance for the RDR2S:
1. Periodically check the continuity of the grounding circuit.
2. Perform operational testing monthly (see "Testing Procedure" on page 37).
3. Replace the lithium battery every five years or after extended (five days)
power interruption (Panasonic CR 2025 or equivalent). See "Real Time
Clock Battery (Lithium Battery) Replacement" on page 37.
4. If installed, replace the lead-acid backup battery every three years (Power
Sonic PS-1270, 12 VDC, 7 Ah for the large enclosure; Power Sonic
PS-1228, 12 VDC, 2.8 Ah for the small enclosure).
36
Specification
24 VDC @ 1.5 amps maximum
12/24 VDC (up to 8 W)
•
2-wire Wiegand (up to 256 bits)
•
5/12/24 VDC (up to 5 W)
•
Red indicator
•
Green indicator
Resistive load
0-12 VDC
2-wire RS-485
•
UL 294 (Access control)
•
UL 1076 (Proprietary alarm unit)
•
CSA/CUL C22.2 No. 205
•
FCC, Class B
•
CE Mark
•
C-Tick
•
DIN rail
•
Flat surface
•
Field wiring assembly and control electronics are on separate
panels to aid in ease of installation
7 H x 4.5 W x 2.25 D inches
(17.5 cm x 11.25 cm x 5.5 cm)
32º to 122º F (0º to 50ºC)
10 to 85% non-condensing
Cabinets require free movement of air over all exposed surfaces