Power Requirements - Johnson Controls S300 Series Hardware Installation Manual

Hide thumbs Also See for S300 Series:
Table of Contents

Advertisement

Hardware Installation

Power Requirements

See the following table for general power requirements. For power requirements for
input and output points, see "External Device Power" on page 10 and "Reader
Power" on page 10.
Parameter
Input voltage
Nominal voltage
Maximum power needed
Output ratings (total for the RDR2S)
Line Voltage Information
If the facility is located in an area where power lines are subject to frequent lightning
strikes, verify with the electric company that the building transformer is equipped
with surge protectors. These, as well as a "crowbar" type of protection, can be
installed at the main service entrance if the building transformer is not equipped
with lightning protection.
While lightning is one cause of power line transients, others can be internal or
external to the building environment. The general application of transient surge
suppression is low-cost insurance to ensure long life of the equipment being
installed.
Wiring Input/Output Devices
Tamper Switch Wiring
The tamper switch connects to a general purpose input point. To be operational, the
tamper switch must be wired to one of the unused input points on any RDR2S in the
enclosure, and programmed in the controller.
14
S300-DIN-RDR2S Module
Value
15 VDC min to 28 VDC max.
24 VDC
36 W
5 VDC at 3 W; 12 VDC at 16 W; 
24 VDC at 14.4 W
This document contains confidential and proprietary information of Johnson Controls, Inc.
24-10239-413 Rev. A
© 2010 Johnson Controls, Inc.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

S300-din-rdr2s

Table of Contents