Siemens SIMATIC ET 200SP Manual page 22

Communication module io-link master cm 4xio-link (6es7137-6bd00-0ba0)
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Parameters/address space
4.2 Declaration of parameters
The following table shows the port parameters for the IO-Link Master CM 4xIO-Link
communication module.
Table 4- 2
Parameters
Port configuration
Operating mode
Length of input data
Length of output data
VendorID**
DeviceID**
Test level / Data storage**
* Ensure that you do not exceed the maximum length of the input and output data for all ports.
Example:
You have selected the configuration 32I/32O. You have assigned 16 bytes of input data to the first
port.
You can still assign a total of 16 bytes of input data to the remaining three ports.
** Only effective if you use the "IO-Link Manual" port mode.
Reference
Additional information on the VendorID and DeviceID can be found on the Internet
(https://support.industry.siemens.com/cs/ww/en/view/109748852).
22
Port parameter (GSD file)
Value range
IO-Link Autostart
IO-Link manual
DI
DQ
Deactivated
depending on the selected I/O
type*
depending on the selected I/O
type*
Manufacturer ID of the connected
IO-Link devices
Device ID of the connected
IO-Link devices
Identical type (V1.0) without
Backup&Restore
Type-compatible (V1.1)
without Backup&Restore
Type-compatible (V1.1) with
Backup&Restore
Type-compatible (V1.1) with
Restore
Communication module IO-Link Master CM 4xIO-Link (6ES7137-6BD00-0BA0)
Default
IO-Link Autostart
depending on the selected I/O
type*
depending on the selected I/O
type*
0
0
Type-compatible (V1.1) with
Backup&Restore
Manual, 10/2017, A5E03856846-AD