6.8.5 SS4 diagnostic functions

LED on CS7
LED on SS4
Hardware - SIMADYN D
Edition 12.2004
HongKong|UK|China
www.aotewell.com
Each receptacle of the CS7 support module has 2 LEDs, which allow
diagnostic of the associated communication module (operating and
fault/error conditions).
LEDs on CS7
Green
Yellow
H10 / H20 / H30
H11 / H21 / H31
Dark
Dark
Flashing
Flashing
Flashing
Dark
Lit
Dark
Lit
Dark
Table 6-4 Functions of the LEDs on CS7
An additional four LEDs for interface diagnostics is provided on the
communications module. However, when installed these LEDs are not
visible.
LED on SS4
H1
Dark / lit:
Flickers / glows:
H2
Dark / lit:
Flickers / glows:
H3
Dark / lit:
Flickers / glows:
H4
Dark / lit:
Flickers / glows:
Table 6-5 Functions of the LEDs on SS4
sales@aotewell.com
Communications support modules
Significance for SS4
Communications module not initialized
RAM test error
Hardware of the communications
module is initialized;
wait for a connection to be established
to the initializing CPU module
DUST / USS initialized
Lit
Data transfer running
Lit
Software error
Significance for SS4
Hex monitor not receiving
Hex monitor receiving data
Hex monitor not transmitting data
Hex monitor transmitting data
DUST/USS interface not transmitting
DUST/USS interface transmitting data
DUST/USS interface not receiving data
DUST/USS interface receiving data