6.9.2 Mounting guidelines and noise immunity
Grounding the
front panel with
CS7
Cable
screening
Other information

6.9.3 Diagnostics LED

CS7 LED for SS5
CS7 LED for SS52
Hardware - SIMADYN D
Edition 12.2004
HongKong|UK|China
www.aotewell.com
We are preparing an Internet page for SIMADYN D.
The front panel of the communications module must be connected to the
front panel of the CS7 using the cables provided with the CS7.
The screen of the data transfer cable (bus cable) must be grounded to a
grounding rail through the largest possible surface area where the cable
enters the equipment.
In addition, the screen in the connector housing must be connected to the
housing. The connector must be tightly screwed to the communications
module.
Further information on EMC and ambient conditions, refer to Section
„General technical data"
Each receptacle of the CS7 support module has 2 LEDs, which allow
diagnostics of the associated communications module (operating- and
error/fault conditions).
LEDs on CS7
Green
Yellow
H10 / H20 / H30
H11 / H21 / H31
Dark
Dark
Dark
Lit
Dark
Flickers
Slow
Dark
flash
Fast
Dark
flash
Lit
Dark
Lit
Lit
Lit
Flickers
LED
Green
H10 / H20 / H30
Dark
CPU stopped
Flashing, 5 Hz
Fatal error:
Read-out the error codes at
sales@aotewell.com
Industry Automation
Communications support modules
Significance for SS5
Processor not initialized
Without database at the bus;
COMSS5 must be parameterized
No database, with bus activity;
COMSS5 must be parameterized
Initialization erroneous;
COMSS5 database erroneous
Initialization phase 1
Initialization phase 2
Correctly connected at the bus; presently
no bus activity
Bus activity
Yellow
H11 / H21 / H31
No bus operation (initialization
phase)
Error on the bus,
e. g. short-circuit:
6
6-43
+86-755-8660-6182