Analog Input Ranges - York YD Series Operation Manual

Optiview control center centrifugal liquid chillers
Table of Contents

Advertisement

FORM 160.69-O1
ISSUE DATE: 9/30/2012
The following table indicates the valid display range
for each of the analog input values. In the event that the
input sensor is reading a value outside of these ranges,
the < or > symbols will be displayed beside the mini-
mum or maximum value, respectively.
ANALOG INPUT
Leaving Chilled Liquid Temperature
Return Chilled Liquid Temperature
Leaving Condenser Liquid Temperature
Return Condenser Liquid Temperature
Evaporator Refrigerant Temperature (Optional)
Discharge Temperature
Oil Temperature
Condenser Pressure
Condenser Temperature*
Evaporator Pressure
Evaporator Temperature*
Oil Sump Pressure
High Speed Thrust Bearing Proximity Position
Refrigerant Level
Drop Leg Refrigerant
*Saturation temperatures are calculated values. They will display XXX if the pressure used for the calculation is out of range.
JOHNSON CONTROLS

ANALOG INPUT RANGES

ENGLISH RANGE
LOW
HIGH
0.0
82.0
0.0
94.1
8.0
133.5
8.0
133.5
0.0
126.1
31.8
226.3
31.8
226.3
0.0
315.0
-98.7
160.1
5.5
77.4
-44.9
64.7
0.0
315.0
8.0
99.0
0.0
100.0
0.0
121.7
SECTION 2 – OPTIVIEW CONTROL CENTER
METRIC RANGE
UNITS
LOW
HIGH
°F
-17.7
27.7
°F
-17.7
34.5
°F
-13.3
56.3
°F
-13.3
56.3
°F
-17.7
52.3
°F
-0.1
107.9
°F
-0.1
107.9
PSIG
0.0
2172.4
°F
-72.6
71.7
PSIG
37.9
533.7
°F
-42.7
18.1
PSIG
0.0
2172.4
MILS
8.0
99.0
%
0.0
100.0
°F
-17.7
49.8
2
UNITS
°C
°C
°C
°C
°C
°C
°C
KPAG
°C
KPAG
°C
KPAG
MILS
%
°C
29