Display Messages - York YD Series Operation Manual

Optiview control center centrifugal liquid chillers
Table of Contents

Advertisement

FORM 160.69-O1
ISSUE DATE: 9/30/2012
The Status Bar of the Display contains a Status Line
and, beneath it a Details Line. The Status Line contains
a message describing the operating state of the chill-
er; whether it is stopped, running, starting or shutting
down. The Details Line displays Warning, Cycling,
Safety, Start Inhibit and other messages that provide
further details of the Status Bar messages. The Sta-
tus Messages listed below are displayed on the Status
Line. All other messages are displayed on the Details
Line.
To aid in the meaning of the message, messages are
displayed in different colors as follows:
Normal Operation messages - Green
Warning messages - Yellow
Cycling Shutdown messages - Orange
Safety Shutdown messages - Red
Status Messages
"SYSTEM READY TO START"
The chiller is shut down but will start upon receipt of a
Local or Remote start signal.
"CYCLING SHUTDOWN – AUTO RESTART"
The chiller is shut down on a CYCLING shutdown.
The cause of the shutdown is still in effect and is dis-
played on the Details line of the Status Bar. The chiller
will automatically restart when the CYCLING condi-
tion clears.
"SAFETY SHUTDOWN – MANUAL RESTART"
The chiller is shut down on a SAFETY shutdown. The
cause of the shutdown is still in effect and is displayed
on the Details line of the Status Bar. The chiller can be
started after the Safety condition clears and the Opera-
tor moves the COMPRESSOR switch to the STOP-
RESET (O) position.
"SYSTEM PRELUBE"
A chiller start has been initiated and the pre-start lubri-
cation is being performed on the Lead compressor. The
Prelube duration is either 50 seconds or 180 seconds,
as configured with a Microboard Program Switch. The
Pre-lube duration must never be changed by anyone
other than a qualified Service Technician. The stan-
dard Prelube duration is 50 seconds.
JOHNSON CONTROLS

DISPLAY MESSAGES

"SYSTEM RUN"
The chiller is running under the condition described in
the Details Line of the Status Bar.
"SYSTEM COASTDOWN"
The chiller has shut down and the Post-run lubrication
is being performed. The Coastdown duration varies
according to the microboard and setup. On 031-01730-
000 microboards, it is 150 seconds for electric motor
applications (standard); 15 minutes for Steam Turbine
applications (enhanced), as determined by Program
Jumper JP36. On 031-02430-000/001 microboards,
the duration varies according to the software used.
With Software version C.OPT.11.02B.xxx (and ear-
lier), the Coastdown duration is determined by the
setting of the COASTDOWN (standard or enhanced)
Setpoint on the SETUP Screen. With Software version
C.OPT.11.03.01.004 (and later), the duration is de-
termined by the setting of the COASTDOWN TIME
setpoint. It is programmable over a range determined
by the CHILLER STYLE/COMPRESSOR setpoint
(for style AB/J1-J5, the range is 150 (default) to 900
seconds. For all others, the range is 240 (default) to
900 seconds.
"SYSTEM START INHIBIT"
The chiller is prevented from being started due to the
reason displayed on the Details Line of the Status bar.
"SYSTEM
DOWN"
Displayed while the Pre-rotation Vanes and Discharge
Valves are closing during a soft shutdown of the entire
chiller. A soft shutdown is performed on the running
compressors for the following shutdowns:
"Leaving Chilled Liquid Temperature – Low Tem-
perature"
"Remote Stop" (ISN, Analog Remote or Digital
Remote)
"Control Panel-Schedule"
"Multiunit Cycling-Contacts Open"
"System Cycling #1-Contacts Open"
"System Cycling #1-Contacts Open"
"Discharge #1-Valve Not Closed"
"Discharge #2-Valve Not Closed"
Operator initiated at Keypad
SECTION 2 – OPTIVIEW CONTROL CENTER
UNLOADING
BEFORE
2
SHUT-
115