FortiGate-7040E chassis
Each PSU is designed to be installed in a Telecom data center or similar location that has available -48VDC power fed
from a listed 40A circuit breaker. To improve redundancy you can connect each power supply to a separate power
circuit.
DC power cables are intended to be used only for in-rack wiring, must be routed away from sharp edges, and must be
adequately fixed to prevent excessive strain on the wires and terminals.
DC terminals accept UL approved ring terminals for 8/M4 stud with ext ring diameter < 9.8 mm. DC cables must be a
minimum of 8 AWG.
The following table lists some key power data for each PSU.
Max Inrush Current
Max Inrush Current Duration
Input Voltage
Input Current
DC PSU (power connector cover removed)
+ (Red)
Power
Connector
- (Black)
Power
Connector
PSU LED States
State
Off
Flashing Green
Green
Amber
Flashing Amber
FortiGate-7040E System Guide
50A
200ms
-40V to -72V
Average: 12.5A@48V for each PSU, Max: 44A
LED
Latch
Description
DC power not connected.
The PSU is in standby mode, not supplying power to the chassis.
Normal Operation with DC power connected.
Input voltage outside of normal operating range, PSU fan not operating, or output
voltage outside of normal operating range.
Warning that power input or output is close to outside of normal operating range.
PSU should be replaced.