Field specification setting mode of wired remote controller
Classification
Outing mode
Others
Economic DHW mode
(Power peak control)
Ratio of hot water supply
compare to heating

Functions that requires setting according to field specification

f Code: 10**
f
- Upper and lower temperature limits for Heating (Water out, Room), Cooling (Water out, room), DHW (Tank) mode
- 1011 : Maximum Value of cooling leaving water temperature setting in wired remote controller
- 1012 : Minimum Value of cooling leaving water temperature setting in wired remote controller
- 1021 : Maximum Value of cooling indoor's room temperature setting in wired remote controller
- 1022 : Minimum Value of cooling indoor's room temperature setting in wired remote controller
- 1031 : Maximum Value of heating leaving water temperature setting in wired remote controller
- 1032 : Minimum Value of heating leaving water temperature setting in wired remote controller
- 1041 : Maximum Value of heating indoor's room temperature setting in wired remote controller
- 1042 : Minimum Value of heating indoor's room temperature setting in wired remote controller
- 1051 : Maximum Value of hot water tank temperature setting in wired remote controller
- 1052 : Minimum Value of hot water tank temperature setting in wired remote controller
24
Function
Temperature of cooling
Room Temperature of
Temperature of heating
Temperature of auto
heating WL1 water
Temperature of auto
heating WL2 water
Temperature of hot
Temperature of hot
Smart grid
determined based
on the value of the
A)7 means Heating
capacity=Hot water
Code
(Main
Detail
+ sub
menu)
5011
water oulet
5012
cooling Mode
5013
leaving water
Indoor heating
5014
temperature
5017
5018
5019
water Tank
5021
water Tank
Operation
5041
Heat source for
5042
operation limit
Contact Logic
5043
A/7 (Ratio is
5061
capacity
Basic
Min.
Max.
-
-
-
-
-
-
25
25
80
16
16
30
25
25
80
25
25
80
35
35
75
5
0
40
0 (No)
0
1 (Yes)
0 (All)
0
2
1 (High) 0 (Low)
1
7
1
7
Step
Unit
1
°C
1
°C
1
°C
1
°C
1
°C
1
°C
1
°C
1
°C
-
-
1
-
-
-
1
-