DIAG LED
Table 4- 2
DIAG LED
Channel status LED
Table 4- 3
Channel status
CNT LED
Table 4- 4
Digital input module DI 8x24VDC HS (6ES7131-6BF00-0DA0)
Equipment Manual, 11/2019, A5E35243810-AD
DIAG LED fault/error display
Meaning
Backplane bus supply of the ET 200SP not OK
Off

Module parameters not assigned
Flashes
Module parameters assigned and no module diagnostics
On
Module parameters assigned and module diagnostics
Flashes
Status display of the channel status LED
Meaning
LED
Process signal = 0
Off

Process signal = 1
On
Status display of the CNT LED
CNT LED
Meaning
Counting operating mode disabled
Off

Counting operating mode enabled
On
Counting operating mode (CNT)