Settings (Fun Mode Operation); Setting Item List - Omron EQUO Series User Manual

Portable power monitor; power sensor station;
Hide thumbs Also See for EQUO Series:
Table of Contents

Advertisement

4.2

Settings (FUN Mode Operation)

Enter FUN mode to make measurement and recording settings on the unit

4.2.1 Setting Item List

The following list shows the setting items available in FUN mode.
Display Item
CLEAR
CYCLE
UNIT
STRIG
STIME
TIMER
ETRIG
(ON)
ETIME
ELPSD
MODE
REC
INTEG
USECH
Display
Setting Item
Ranking clear
Recording
interval
Number of Power
Sensors/
Monitors connected
Start trigger
Start time
End trigger
End time
Elapsed time
Measurement
mode
Recording mode
Integrated power
reset interval
The number of
channels to use
4-1
3. Check and Preparation
Setting Value
A press of the REC key
displays "CLEAR". Another
press of the REC key clears
the ranking.
1s (sec.)/2s/5s/10s/20s/
30s/1min.
This setting item is not
displayed when the
measurement mode is
HISPD on ZN-CTX21.
1 to 31
OFF/TIME
00:00 to 23:59
OFF/TIME/ELPSD
00:00 to 23:59
0.05 (0 min. 5 sec.) to
999.59 (999 min. 59 sec.)
NORM/SLEEP/HISPD
The unit reset itself and
restarts when the MODE key
is pressed to change the
operation mode after a set
value is applied.
CONT/RING
OFF/30min./1h (hrs.)/24h
"30min.": Integrated power is
reset to zero at 0 and 30 min.
of every hour; "1h": reset at 0
min. of every hour; "24h":
reset at 0:00 every day. The
integrated power up until the
moment of reset is recorded
in the ranking log before it is
cleared to zero.
Only ZN-CTX21 records
integrated power in the
ranking log up to the moment
of zero reset.
After the INTEG setting is
changed, the unit resets itself
and restarts, clearing the
ranking, when the operation
mode is changed by pressing
the MODE key.
1CH/2CH/3CH
Factory
Default
-
*1
1s
● ●
*2
10s
1
OFF
00:00
OFF
00:00
0.05
SLEEP
CONT
● ●
OFF
● ●
1CH

Advertisement

Table of Contents
loading

This manual is also suitable for:

Equo zn-kmx21Equo zn-ctx21