Digital Inputs - Siemens SITRANS L Compact Operating Instructions

Controllers with ultrasonic transducer inputs
Table of Contents

Advertisement

5.2.12

Digital inputs

The digital inputs can be powered from the internal DC power supply (terminal 30), or the
they can be powered from an external power supply.
Digital inputs used with internal DC power supply
Note
Proper connection for use with internal DC power supply
Terminals 33 and 34 must be connected together.
Digital inputs used with external power supply
SITRANS LT500 with ultrasonic transducer inputs
Compact Operating Instructions, 02/2024, A5E52021877-AA
DC power supply for positive digital inputs
Positive input for digital input 1
Positive input for digital input 2
Common negative for digital inputs
Connecting
5.2 Connecting SITRANS LT500
41

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sitrans lt500

Table of Contents