Samson TROVIS 3730-3 Mounting And Operating Instructions page 30

Electropneumatic positioner with hart communication
Hide thumbs Also See for TROVIS 3730-3:
Table of Contents

Advertisement

Design and principle of operation
Signal state
Static destruction limit
Inductive limit contacts
Version
Measuring plate not
detected
Measuring plate
detected
Static destruction limit
Permissible ambient
temperature
Binary input (switching behavior configured in TROVIS-VIEW software)
Active switching behavior (default setting)
Connection
Open-circuit voltage
Current draw
Contact
Passive switching behavior
Connection
Voltage input
Static destruction
limit
Current draw
Switching voltage
Forced venting
Version
Voltage input
Input resistance
Active
Signal
state
Not active
Static destruction limit
30
≤1.0 mA (non-conducting)
≥2.2 mA (conducting)
32 V DC/24 V AC
For connection to switching amplifier according to EN 60947-5-6, SJ2-
SN proximity switches, reverse polarity protection
≥3 mA
≤1 mA
20 V DC
–50 to +85 °C
For external switch (floating contact) or relay contact
Max. 10 V (when contact is open)
Max. 100 mA (pulsed when contact is closed)
Closed: R <20 Ω; open: R >400 Ω
For externally applied DC voltage, reverse polarity protection
0 to 30 V
40 V DC
3.7 V at 24 mA
Closed: <1 V; open: >6 V
Galvanic isolation, reverse polarity protection
0 to 24 V DC
≥7 kΩ
Ue <11 V
Ue >15 V
38 V DC/30 V AC
R = 10 kΩ (non-conducting)
R = 348 Ω (conducting)
16 V DC/50 mA
EB 8484-3 EN