Samson TROVIS 3730-3 Mounting And Operating Instructions page 117

Electropneumatic positioner with hart communication
Hide thumbs Also See for TROVIS 3730-3:
Table of Contents

Advertisement

Menu
Detected nominal range
Initialization mode
Volume booster
Reversing amplifiers
Fail-safe position
Set point (open-loop
control)
Adopt valve position 1
Valve position 1
Adopt valve position 2
Valve position 2
Current valve position
Direction of rotation
Start initialization
Start zero calibration
EB 8484-3 EN
Adjustment range/values [default setting]/description
7.9
Determined nominal range for rotary actuators displayed.
7.10
[MAX]: Travel/angle of the closure member from the CLOSED
position to the opposite stop in the actuator.
NOM: Travel/angle of the closure member measured from
the CLOSED position to the indicated OPEN position.
MAN: Manually selected range
SUB:
Substitute calibration (without initialization)
7.11
If the positioner is combined with a volume booster, this
parameter must be set accordingly.
[Not available]/Available
7.12
If a reversing amplifier is connected to the positioner, this
parameter must be set accordingly.
[Not available]/Available
7.13
Reading of the ATO/ATC slider switch position (see
section 7.2)
–90.0 to 90.0° [–30.0°]
7.14
Manually adjusted first end position of the valve in MAN
7.15
initialization mode
Confirm to adopt.
7.16
Reading only (lever position in degrees)
7.17
Manually adjusted second end position of the valve in MAN
initialization mode
Confirm to adopt.
7.18
Reading only (lever position in degrees)
7.19
–25.0 to 125.0 % [0.0 %]
7.20
Counterclockwise/[Clockwise]
Determine the lever's direction of rotation. For example:
The valve closes when the plug stem moves downward. This
action causes the positioner's lever to turn counterclockwise
(when looking at the display).
ÎSetting: Counterclockwise
7.21
Confirm to start.
7.22
Confirm to start.
Appendix
117