Advertisement

Appendix
Menu
Reason for fail-safe
position
Change reading direction 5
User level
Start-up
Actuator
Pin position
Pin position for linear
actuator
Pin position for rotary
actuator
Pin position for linear
actuator (expert)
Nominal range
Nominal range for linear
actuator
Nominal range for rotary
actuator
Nominal range for linear
actuator (expert)
Max. nom. range
116
Adjustment range/values [default setting]/description
4
Reason for change to fail-safe position displayed. The param-
eter is only displayed in the event of a change to the fail-safe
position.
Reading direction
The reading direction of the display is turned by 180°.
6
[On-site (read only)]/On-site
The option to change data is unlocked (revoked if no settings
are entered within five minutes).
7
7.1
[Linear actuator]
Rotary actuator
Linear actuator (expert)
Select type of actuator: linear actuator (expert) with separate
setting options for pin position and nominal range.
Follower pin must be mounted in the proper position depend-
ing on the valve travel/opening angle (see section 3.6 on
page 26).
7.2
[None]/17/25/35/50/70/100/200/300 mm
7.3
90°
7.4
[10] to 655 mm
The pin position is continuously adjustable within the specified
range.
The possible adjustment range depends on the selected pin po-
sition. If no pin position has been entered, Nominal range is
only available for the Linear actuator (expert) actuator type
(see travel tables on page 26).
7.5
60.0 to 300.0 [200.0]
24.0 to 100.0° [90.0°]
7.6
[3.6] to 655.0 mm
7.7
7.8
Maximum possible nominal range displayed, depending on
values entered for pin position and nominal range.
EB 8484-3 EN