Appendix
Menu
Valid initialization
Initialization mode
Actuator
Pin position
Pin position
Pin position
Nominal range
Nominal range
Volume booster
Reversing amplifiers
Fail-safe position
T98 (supply air)
T98 (venting)
Loop gain (fill with air)
Loop gain (venting)
118
Adjustment range/values [default setting]/description
7.27
The Valid initialization folder lists parameter values used for
the last initialization of the positioner. In the event of a failed
initialization, the values of the last successful initialization re-
main saved in this folder even if the parameters have changed
in the mean time. These parameter values are only overwritten
when a further initialization has been successfully completed.
All listed parameters are set to their default setting on the first
start-up of the positioner.
7.27.1
Reading of initialization mode entered in 7.10.
7.27.2
Reading of actuator type entered in 7.1.
7.27.3
Reading of pin position entered in 7.2.
7.27.4
Reading of pin position entered in 7.3.
7.27.5
Reading of pin position entered in 7.4.
7.27.6
Reading of nominal range entered in 7.5/7.7.
7.27.7
Reading of nominal range entered in 7.6.
7.27.8
Reading of volume booster entered in 7.11.
7.27.9
Reading of reversing amplifier entered in 7.112.
7.27.10
Reading of the ATO/ATC slider switch position
7.27.11
Time [ms] required to fill the actuator with air to achieve a step
from 0 to 98 %. The value is determined during initialization.
7.27.12
Time [ms] required to vent the actuator to achieve a step from
0 to 98 %. The value is determined during initialization.
7.27.13
Reading of loop gain (fill with air) entered in 8.4.4.
7.27.14
Reading of loop gain (venting) entered in 8.4.8.
EB 8484-3 EN