Design and principle of operation
Environmental conditions and permissible temperatures
Permissible environmental conditions according to EN 60721-3
Storage
Transport
Operation
Resistance to vibration
Vibrations
(sinusoidal)
Bumps (half sine)
Noise
Recommended
continuous duty
Influences
Temperature
Supply air
Requirements
EMC
Degree of protection
Electrical connections
Cable glands
Terminals
Explosion protection
ATEX, IECEx
28
1K6 (relative humidity ≤95 %)
2K4
–20 to +85 °C: All versions
–40 to +85 °C: With metal cable glands
–55 to +85 °C: Low-temperature version with metal cable glands
Observe the limits in the test certificate for explosion-protected versions.
According to DIN EN 60068-2-6:
0.15 mm, 10 to 60 Hz; 20 m/s², 60 to 500 Hz per axis
0.75 mm, 10 to 60 Hz; 100 m/s², 60 to 500 Hz per axis
According to DIN EN 60068-2-29:
150 m/s², 6 ms; 4000 bumps per axis
According to DIN EN 60068-2-64:
10 to 200 Hz: 1 (m/s²)²/Hz
200 to 500 Hz: 0.3 (m/s²)²/Hz
4 h/axis
≤20 m/s²
≤0.15 %/10 K
None
Complying with EN 61000-6-2, EN 61000-6-3, EN 61326-1 and NAMUR
Recommendation NE 21
IP 66/NEMA 4X
One M20x1.5 cable gland for 6 to 12 mm clamping range
Second M20x1.5 threaded connection additionally available
Screw terminals for 0.2 to 2.5 mm² wire cross-section
See Table 14 on page 31.
EB 8484-3 EN