Appendix
Menu
Angle limitation
Timeout
Zero calibration error
Zero calibration timeout
Zero calibration: shift >>
Configuration
Combination of options
invalid
Forced venting switch
incorrect
130
10.1.1.21
Recommended action:
10.1.1.22
10.1.1.23
Recommended action:
10.1.1.24
10.1.1.25
Recommended action:
10.1.1.26
Recommended action:
10.1.1.27
10.1.1.28
Recommended action:
10.1.1.29
10.1.1.30
Recommended action:
10.1.1.31
Recommended action:
Adjustment range/values [default setting]/
description
The maximum permissible angle of rotation
(±30°) has been exceeded.
Check positioner attachment, lever and pin
position.
Confirm to clear message.
Initialization took too long.
Possible cause: valve blockage.
Check positioner mounting, pin position and sup-
ply air. Check piping and configuration of the
mounting parts.
Confirm to clear message.
The zero calibration could not be completed. The
forced venting may possibly be active.
Check positioner attachment, pin position and
supply air. Check the set operating mode. Search
for the reason why the forced venting was trig-
gered.
Zero calibration took too long.
Check positioner attachment, pin position and
supply air.
Confirm to clear message.
The difference to the previous zero point is too
large.
Check positioner attachment, pin position and
supply air.
Status indicators
Impermissible combination of options
Contact SAMSON's After-sales Service depart-
ment.
Impermissible mounting situation for forced vent-
ing option
Contact SAMSON's After-sales Service depart-
ment.
EB 8484-3 EN