3.8 Walk Test

Walk Test allows the user to test the entire fire alarm system. There are two kinds of Walk Test -
Basic and Advanced, described later in this section.
Before entering Walk Test, note the following:
• For each individual activation, the control panel sends "TEST Axx" (for alarm testing) or
TEST Txx (for trouble testing) to the History buffer, installed printers and CRT-2s so results
can be reviewed.
• Basic Walk Test, Silent – In order to keep the test silent, do not program any of the output
modules with "W" in the Walk Test field.
• Advanced Walk Test - This test overrides a setting of "
activated outputs will sound until panel reset.
• The control panel provides a 1-hour timer for Walk Test mode. When the hour expires with
no activity, the control panel automatically returns to normal operation.
• Walk Test may be exited at any time by pressing the ESC key.
WARNING:
!
Walk Test mode deactivates fire protection. Always observe the following:
1.
2.
WARNING:
!
Physically disconnect all releasing devices before starting Walk Test. It is not sufficient to
disable in any other manner.
NOTE: Walk Test will not start if any devices are active (i.e., fire alarms, security, supervisories
or pre-alarms.) To perform a walk test while a device is active, disable the device and press the
System Reset button.
For information on programming Walk Test field selections, refer to "Modify an Addressable
Monitor Module Point" on page 22 or "Modify NAC Points" on page 24.
56
Prior to Walk Test, secure all protected buildings, and notify the building owner/operator,
fire department, and other pertinent personnel that testing is in progress.
Immediately after Walk Test is completed, notify the same people that testing is complete
and is restored to normal operation.
Do this
Press
*
" (silent) in the Walk Test field. All
NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14
Walk Test