The Network Program

2.3.9 How to Check the Program for Errors (8=
Program Change
Password
• Output points mapped to a zone without a mapped input
• A zone with mapped input points without mapped output points (including Z00 outputs)
• Releasing zone inputs (R0-R9) with no
CKT
• RO-R9 inputs not mapped to
For more information on Releasing Zones, refer to "Releasing Applications" on page 60.
If the Check option detects multiple devices that fail the check, press the
step through the devices. If the Check option displays errors, return to Point Programming
("Modify or Delete a Point (2=point)" on page 19) and correct the errors. The figure below shows a
sample display of program screen that appears after a successful program check:
2.4 The Network Program
Program Change
Password
THRESHOLD CH.A: - Enter H or L, for high or low threshold setting for channel A on the NCM
module.
THRESHOLD CH.B: - Enter H or L, for high or low threshold setting for channel B on the NCM
module.
NODE: - Enter the panel's network node number. The valid network node number range is 1-103.
The number will be entered after the decimal point; the spaces before the decimal point are for
future use.
STYLE7: - Enter N for network style determination (either Style 4 or Style 7) through
autoprogramming. Enter Y to force a Style 7 designation for network wiring.
NOTE: If network Style 7 wiring is determined by autoprogramming, a change in the wiring (for
example, a break in the network wiring) would cause the system to reassess the network wiring
style as 4. If network Style 7 wiring is forced, a break in the wiring will create a trouble message.
NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14
When finished programming, you can use the Check option to search the
program entries for possible errors. From the "Basic Program" screen, press
the 8 key. The Check option searches the program for the following
conditions that can cause errors:
outputs with no R0-R9 inputs mapped to them
MAN
P R O G R A M C H E C K O K .
R E - T E S T P A N E L N O W
From the "Program Change Selection" screen, press the 2 key to display the
"Network" screen, which displays as follows:
T H R E S H O L D C H . A : H ,
N O D E :
CHECK PRG
outputs mapped to them; or
RELEASE CKT
. R
.
ELEASE
0 8 : 3 4 A 0 4 1 5 0 8 T u e
T H R E S H O L D C H . B : H ,
. 0 0 0 , S T Y L E 7 : N ,
Programming
)
RELEASE
or
key to
PREVIOUS
NEXT
< E N T E R >