Releasing Applications
REL CODE BELL Type Code
NOTE: An output with a
Releasing Zone selection (R0-R9); An input circuit mapped to the same Releasing Zone.
NOTE: For instructions on programming Switch Inhibit, Silenceable, and Walk Test, refer to
"Modify NAC Points" on page 24.
The following contains information needed to program a Release Code Bell circuit for a NAC
Description
A NAC programmed to pulse an audio or visual device as follows:
• 20 ppm when a the initial zone of a cross-zone activates.
• 120 ppm when a Cross Zone is satisfied.
• Steady when a release occurs.
Programming
1.
Select a NAC (refer to "Modify NAC Points" on page 24) to use as a Release Code Bell
Circuit.
2.
Select the
3.
Select the Releasing Zone (R0-R9) for your releasing application.
4.
Press the
screen.
Example
A programming example of a NAC programmed as a Release Code Bell circuit for Releasing Zone R5.
90
REL CODE BELL
Type Code, as shown in the following example (NAC shown).
REL CODE BELL
P R O G R M R E L C O D E B E L L F R O N T H A L L W A Y N O . 3
Releasing Zone
selection (R5 shown)
Switch Inhibit: I = selected
key to save, then press the
ENTER
Monitor
Detector
Module
Type Code
REL CODE BELL
B01
B03
A NAC programmed with the
simultaneously with other outputs programmed for R05 (B01 and B02).
Figure A.20 NAC Configured as a Release Code Bell Circuit
Type Code requires the following selections: A
Type Code selection:
R 5 _ _ _ _ _ _ _ _
key two times to return to the Program Change
ESC
Detector
R05
B02
Type Code activates
REL CODE BELL
NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14
How to Program a Releasing Zone
.
REL CODE BELL
I * *
B 0 3
Walk Test
Selection: * = off
Silenceable: * = off
Detector
Control
Module