4: Change A Password (3= Passwd ) - Honeywell Notifier NFS2-640/E Programming Manual

Fire alarm control panel
Hide thumbs Also See for Notifier NFS2-640/E:
Table of Contents

Advertisement

Basic Program
Field
Silenceable
Walk Test
2.
When finished modifying a point, press the
select another point.
2.3.4 Change a Password (3=
Program Change
Password
To change a password, follow the instructions below:
To
Change the Program Change
password
Change the Status Change
password
Save the password
Leave the Change Password
screen without changing a
password
NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14
Table 2.6 Modifying a NAC Programming Selections (2 of 2)
Description
Specifies if an operator can manually
silence an activated output
Specifies if outputs sound during Walk
Test
Password Change lets you select a custom Program Change (high level) or
Status Change (low level) password. From the "Basic Program" screen, press
the 3 key to display the "Change Password" screen.
.
C H A N G E P A S S W O R D
# , N N N N N , E = S T A T U S
Entry area for new password
Table 2.7 Changing a Password
Set as follows:
Type in one of the following values.
* = output nonsilenceable
F = silenceable, resound by fire alarm
U = silenceable, resound by supervisory alarm
B = silenceable, resound by security alarm
T = silenceable, resound by trouble
O = silenceable, does not resound
If the "Strobe" Type ID is used with System Sensor,
Gentex or Wheelock Strobe synchronization,"*" will
silence the horn portion only, and resound will occur only
by fire alarm. F, U, B, T, or O will silence the entire circuit,
and resound will occur according to the above definitions.
Type in one of the following values.
W = devices sound (Basic Walk Test) - default
* = devices do not sound (Silent Walk Test)
key; then press the
ENTER
)
PASSWD
* , N N N N N , E = P R O G R A M
Press
Then
Enter the new Program Change
password. Use five digits, no characters.
Enter the new Status Change password.
Use five digits, no characters.
The Verify Password screen appears.
Press
ENTER
The Basic Program screen appears.
Programming
or
key to
NEXT
PREVIOUS
to verify.
25