Basic Program
2.3.1 Clear Memory (0=
Program Change
Password
1.
From the "Basic Program" screen, press the 0 (zero) key to display the Clear Program screen.
The control panel prompts for verification as shown below:
2.
Press the
without clearing.
2.3.2 Autoprogram the Control Panel (1=
Purpose
The Autoprogram option identifies all addressable devices connected to the control panel. Devices
include addressable detectors and modules connected to SLC 1 or SLC 2, and NACs. You can use
the Autoprogram option to create a new program and add or remove devices. A summary of the
Autoprogram functions, when to use the functions, and where to find information on using the
functions is found below:
Autoprogram Function
Create a new program for
the control panel
Add one or more
SLC-connected detectors
and modules to an
existing program
Remove one or more
SLC-connected detectors
and modules from an
existing program
View system defaults
Create a New Program for the Control Panel
Program Change
Password
NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14
)
CLR
The Clear option removes all programming information from control panel
memory. If installing the control panel for the first time, use option 0 to clear
control panel memory. To do so, follow these steps:
P R E S S E N T E R T O C L E A R E N T I R E P R O G R A M
O R E S C A P E T O A B O R T
key to clear control panel memory or press the
ENTER
Control Panel Configuration
A new control panel or a control panel with no
existing program in memory.
A program exists in memory and you want to
add a detector or module to the existing
program—without modifying information for
existing detectors and modules.
A program exists in memory and you want to
remove an installed detector or module from
the existing program—without modifying
information for existing detectors and
modules.
A program exists in memory and you want to
view system settings assigned during
Autoprogram, such as custom labels,
passwords, and so on.
This section covers how to use the Autoprogram option to create a new
program for the control panel. The control panel will identify all addressable
detectors and modules connected to the SLC.
To create a new program for the control panel, follow these steps:
key to exit the screen
ESC
)
AUTO
Refer to...
"Create a New Program for the
Control Panel" on page 15
"Add a Device to the Program"
on page 16
"Remove a Device from the
Program" on page 17
Page 19 "Change Autoprogram
Default Value" to see the system
defaults