Type Codes
1
CLIP Mode only
2
Requires approval of AHJ.
3
Not suitable for Canadian applications.
4
LED representation of a CO alarm may be performed using an ACS annunciator.
5
Photo element can be programmed as latching or tracking for all Photo/Co devices programmed as this type ID via VeriFire Tools.
F.4.3 Type Codes for Monitor Modules
A list of monitor module Type Codes, which you can use to change the function of a monitor
module point.
Type Code
Point
Type
MONITOR
fire alarm
PULL STATION
fire alarm
RF MON MODUL
fire alarm
RF PULL STA
fire alarm
SMOKE CONVEN
fire alarm
SMOKE DETECT
fire alarm
WATERFLOW
fire alarm
WATERFLOW S
supervisory
ACCESS MONTR
non-alarm
AREA MONITOR
security
AUDIO SYSTEM
trouble
EQUIP MONITR
security
RF SUPERVSRY
supervisory
SECURITY
security
LATCH SUPERV
supervisory
TRACK SUPERV
supervisory
SYS MONITOR
security
TAMPER
supervisory
ACK SWITCH
non-alarm
ALLCALL PAGE
non-alarm
DRILL SWITCH
non-alarm
EVACUATE SWITCH non-alarm
FIRE CONTROL
non-alarm
NON FIRE
non-alarm
PAS INHIBIT
non-alarm
POWER MONITR
trouble
RESET SWITCH
non-alarm
SIL SWITCH
non alarm
TELE PAGE
non-alarm
DISABLE MON
disable
TROUBLE MON
trouble
ABORT SWITCH
non alarm
MAN RELEASE
fire alarm
MANREL DELAY
fire alarm
SECOND SHOT
fire alarm
Blank
fire alarm
HEAT DETECT
fire alarm
114
Table F.1 Intelligent Detector Type Codes (3 of 3)
Table F.2 Type Codes for Monitor Modules (1 of 2)
Point Characteristics
Latching
Point Function
(Y/N)
Y
Lights fire alarm LED and activates CBE
Y
Lights fire alarm LED and activates CBE
Y
Lights fire alarm LED and activates CBE
Y
Lights fire alarm LED and activates CBE
Y
Lights fire alarm LED and activates CBE
Y
Lights fire alarm LED and activates CBE
Y
Lights fire alarm LED and activates CBE
Y
Lights supervisory LED and activates CBE
N
Activates CBE
Y
Lights security LED and activates CBE
N
Lights trouble LED
N
Activates CBE
N
Lights Supervisory LED
Y
Lights security LED
Y
Lights supervisory LED
N
Lights supervisory LED
Y
Lights security LED and activates CBE
Y
Lights supervisory LED, activates CBE
N
Performs Acknowledge function, no CBE
N
Activates all speaker circuits, no CBE
N
Performs Drill function
N
Performs Drill function
N
Activates CBE
N
Activates CBE
N
Inhibits Positive Alarm Sequence
N
Indicates trouble
N
Performs Reset function
N
Performs Signal Silence function
N
Performs function of Page Button on FFT-7
N
When a point with this type code activates,
it will create a disable on the panel for that
point. No CBE generated.
N
Indicates Trouble
N
Indicates Active at the panel
Y
Lights Fire Alarm LED and activates CBE
Y
Lights Fire Alarm LED and activates CBE
Y
Indicates Active at the panel and activates
CBE
Y
Lights fire alarm LED and activates CBE
Y
Lights fire alarm LED and activates CBE
Device Function
Alarm-monitoring device
Manual fire-alarm-activating device, such as a pull
station
Wireless alarm-monitoring device
Wireless manual fire-alarm-activating device, such as a
pull station
Indicates activation of a conventional smoke detector
attached to an FZM-1
Indicates activation of a conventional smoke detector
attached to an FZM-1
Monitor for waterflow alarm switch
Indicates supervisory condition for activated waterflow
switch
Used for monitoring building access
Monitors building access
Used for monitoring audio equipment
Used for recording access to monitored equipment
Monitors a radio frequency device
Indicates activation of security alarm
Indicates latching supervisory condition
Monitors for waterflow tamper switches for alarm points
Monitors equipment security
Indicates activation of tamper switch
Silences panel sounder, gives an Acknowledge
message on the panel LCD
Performs AMG-1 All-call
Activates silenceable outputs
Activates all silenceable outputs
Used for non-fire activation of outputs
Used for building energy management
Inhibits Positive Alarm Sequence
Monitors auxiliary power supplies
Resets control panel
Turns off all activated silenceable outputs
Allows remote paging to a fire area
Module can not be disabled via ACS, Alter Status, or
over the network.
Monitors trouble inputs
Aborts activation of a releasing zone
Indicates activation of a monitor module programmed to
releasing zone to perform a releasing function
Indicates activation of a monitor module programmed
for a release output
Provides second activation of releasing zone after soak
timer has expired.
Monitors for a device with no description
Monitors for conventional heat detector
NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14