Devices

1.4 Devices
1.4.1 Isolator Modules
Isolator Modules permit a zone of detectors and modules to be fault isolated from the remainder of
the SLC loop, allowing critical components to function in the event of a circuit fault. Isolator
modules are required to meet the requirements of an NFPA Style 7 circuit.
I300 - Single fault isolator module
ISO-6 - Six fault isolator module
1.4.2 Monitor Modules
Addressable modules that allow the control panel to monitor entire circuits of conventional alarm
initiating devices, such as manual pull stations, smoke detectors, heat detectors, waterflow and
supervisory devices.
MMF-300 - Monitors a Style B (Class B) or Style D (Class A) circuit of dry-contact input devises.
MMF-300-10 - Monitors ten (10) Style B (Class B) or five (5) Style D (Class A) normally open
contact device circuits.
MMF-301 - Same as the MMF-300 except offered in a smaller package for mounting with Style B
wired devices. This module does not have an LED.
MMF-302 - Monitors a single IDC of two-wire smoke detectors.
MMF-302-6 - An addressable module that provides an interface between the control panel and six
(6) Style B (Class B) or three (3) Style D (Class A) IDCs of two-wire smoke detectors.
MDF-300 - Similar to MMF-300, but provides for two independent Style B IDCs.
1.4.3 Control Modules
Through the CMF-300 addressable control module, the control panel can selectively activate a
Notification Appliance Circuit (NAC).
CMF-300-6 - Similar in operation to the CMF-300, except it can activate six (6) Style Y (Class B)
or three (3) Style Z (Class A) NACs.
1.4.4 Relay Modules
The CRF-300 addressable relay module provides the control panel with a dry-contact output for
activating a variety of auxiliary devices.
CRF-300-6 - Similar in operation to the CRF-300, except it provides six (6) Form-C relays.
1.4.5 Multiple Input/Output Modules
The CDRM-300 addressable multiple input/output module monitors two (2) Style B input devices
and provides two (2) independent Form-C relay contacts.
1.4.6 Intelligent Detectors
AD350 - A multicriteria smoke sensor that combines a photoelectric sensing chamber and 135°F
(57.2°C) fixed temperature heat detection. The sensor uses addressable communication to transmit
smoke density and other information to the control panel. It adjusts its detection parameters and
alarm threshold depending on the ambient conditions it samples in its environment.
AD355 - A multicriteria smoke sensor that combines a photoelectric sensing chamber and 135°F
(57.2°C) fixed temperature heat detection. The sensor uses addressable communication to transmit
smoke density and other information to the control panel. It adjusts its detection parameters and
alarm threshold depending on the ambient conditions it samples in its environment.