How To Enable/Disable Master Alarms, Fire Relay And Evac. Input; How To Enable Or Disable And Set A Sector Activation Control - Honeywell GENT Nano panel-based Commissioning Instructions

Fire detection and alarm system
Table of Contents

Advertisement

How to enable/disable Master alarms, Fire relay and Evac. input

You can manually enable or disable the master alarms, fire relay and evacuate input. You can also view the current state of master alarms, fire relay and evacuate input. You will need to be at access
level 2 or above to enable or disable these functions.
Menu
User
Select
Alarms

How to enable or disable and set a Sector activation control

You can manually enable or disable alarm activation control and view current state of the sector. You will need to be at access level 2 or above to enable or disable sectors. You will need to be at
access level 3 or above to change the sector activation control..
Menu
Select
User
4188-949 issue 3_05/10_Nano Comms inst.
Select
>
Other
Select
Alarms
>
Sectors
Select Activation
AL2
At
view you can only view the set Activation Control
AL3
At
and above you can change the Activation Control to:
- SILENCE
- TEST
- CLASS
- ALERT
or - EVACUATE
10:15 Tue 16/02/10
Alarm Status
State
Enable Status
Master Alarms : INACTIVE
[ ENABLED ]
Fire Relay
: INACTIVE
[ ENABLED ]
Select
Evacuate Input: INACTIVE
[ ENABLED ]
Save
Disablement
[amber LED]
Sounder
Disablement
[amber LED]
Here the 'Sounder Disablement'
LED is only lit when the
Master Alarms are disabled.
Select a 'Sector' from a range 1 to 16
Sector: [ 1]
Label : Sector Label
Select
Activation Control :
Status Control :
Current State : IDLE
Save
Nano panel based system
Save
To scroll range
Quit
Set Alarm status of:
'Master Alarms' Enable Status to ENABLED (Factory default setting) or DISABLED
'Fire Relay' Enable Status to ENABLED (Factory default setting) or DISABLED
'Evacuate Input' (INACTIVE) to ENABLED (Factory default setting) or DISABLED
To scroll range
10:15 Tue 16/02/10
SILENCE
Save
[ENABLED
]
[amber LED]
Quit
[amber LED]
Select 'Sector' status:
Sector 'ENABLED' (factory default setting) or Sector 'DISABLED'
To move to
the next setting
To move to
the next setting
Disablement
Sounder
Disablement
63

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents