How To View Or Change 'Device Configuration - Honeywell GENT Nano panel-based Commissioning Instructions

Fire detection and alarm system
Table of Contents

Advertisement

How to view or change 'Device configuration'

&
The Nano panel recognises the 34420 Interface Unit as having 1-Output channel only. The 'confirmation Input' channel of this interface unit is not recognised nor used when
this unit is connected to the Nano loop circuit.
Two methods are shown for making changes to device configuration.
Method 1 at access level 3 or above
Menu
Settings
Select
UNCONNECTED
N/O SUPERVISORY #
RELAY OUTPUT*
DELAYED N/C FIRE
LED OUTPUT*
DELAYED N/O FIRE
N/C FIRE
DELAYED N/C FAULT
N/O FIRE
DELAYED N/O FAULT
N/C FAULT
DELAYED N/C SUPERVISORY #
N/O FAULT
DELAYED N/O SUPERVISORY #
N/C SUPERVISORY #
CONVENTIONAL ZONE
* Only applicable for 4 channel interface
#
SILENCE ALARMS
SYSTEM RESET
DISABLE ZONE
DISABLE SECTOR
DAY/NIGHT SWITCH
VERIFY ALARMS
ACTION SECTOR
ZONE IN TEST
CLASS CHANGE
EXTERNAL EVAC
Method 2 at access level 4
Menu
Engineering
Select
4188-949 issue 3_05/10_Nano Comms inst.
Select a 'Device' from a range 1 to 127
This example shows the display of a
Dual Optical Sensor Sounder and Strobe
Select
Loop
>
Devices
Select an Output level for the device from a range:
-0dB, -3dB, -6dB, -9dB, -12dB or -15dB, -18dB, -21dB
After making changes to this form you will need to back-up the data to
memory. Ensure the write protect link P9 on the MCB is configured in
the ENABLED position to allow back-up of data.
Loop
>
Select
Select
Map
To move to
To scroll the
next setting
range
Edit the 'Device' label
'Find Device' ON / OFF option
Set 'Device' assignment to 'Zone' and 'Sector'
from a range 1-16.
10:15 Tue 16/02/10
Device : [
1] Settings
Find [OFF]
Label:[Device Label
2
Type: O H Sensor + Strobe/Speech
Assigned to Zone:[ 1]
Sect: [ 1]
Sensitivity States
Night: [ 0]
Day:[ 0]
Output Level:[-0dB ]
Mode:[TONE]
Save
Select 'TONE' or
'VOICE' mode
Select 'Sensor State' for 'Day' and 'Night' modes
from a range - 0 (factory default setting) to 15
Loop Map
1+
Select
View
Select
2
3
4
Select
Nano panel based system
]
ML: [OFF]
Save
Quit
Monitored Line
'ON' or 'OFF'
(factory default
setting).
10:15 Tue 16/02/10
9
Device
1
Settings
9
Device
2
9
Device
3
9
Device
4
Quit
Select
37