How To 'Back-Up' Site Data To Flash Memory; How To 'Restore' Configuration Data From Flash Memory - Honeywell GENT Nano panel-based Commissioning Instructions
Once the panel has allocated addresses to all the loop devices and the loop has started you will need to back-up the site data to the Flash memory at the panel. Any subsequent changes to the
configuration and labels during commissioning will also need to be backed-up. When the commissioning tool is used to transmit the custom configuration to the panel, the new data at the panel must be
backed-up to the panel memory. You will need to be at access level 3 or above to back-up site data to flash memory.
Menu
Select
Engineering
Engineering
>
Ensure the write protect link P9 on the MCB in configured in the
ENABLED position to allow back-up of data to memory.
How to 'Restore' configuration data from Flash memory
If for some reason the changes made to the configuration since previous back-up is not known then you can restore the previous back-up. You will need to be at access level 3 to restore configuration