How To View The 'Loop Status; How To View The 'Loop Map' And 'Enable / Disable' Devices - Honeywell GENT Nano panel-based Commissioning Instructions

Fire detection and alarm system
Table of Contents

Advertisement

How to view the 'Loop Status'

The loop status provides information on the current status of the loop, total number of devices found on the loop, wiring status and the address of the last device on the loop.
You will need to be at Access level 2 or above to view loop status.
Menu
User
Select
Loop
You can also view the loop status at Access level 4.
Menu
Engineering
Select

How to view the 'Loop Map' and 'Enable / Disable' Devices

The 'Loop map' is a list of devices installed between end-1 and end-2 of the loop wiring. It shows devices in sequential order starting from End-1 of the loop. This is the first check against theas fitted
wiring drawings, that confirms the number of devices installed in the protected premises. It is possible to display or print a loop map. The printout is only possible if a printer is connected. In addition to
this it is possible to scroll to a selected device and view the device information. After viewing the device details you can return to the loop map by selection the'Back' option. You will need to be at
Access level 2 or above to view the loop map.
&
The display of Individual 'Sounder disablement' information will be suppressed when the panel enters a fire condition, consequently in this condition the
panel will fail to meet the requirements of EN54-2 clause 9.4.2 a) amendments.
Menu
User
Select
Loop
4188-949 issue 3_05/10_Nano Comms inst.
Status
>
Select
Select
Status
Loop
>
Select
Select
>
Select
Select
Devices
Loop Map
1+
+
A ' ' after the device number
20
indicates the device is
SAFE addressed.
23
The Devices 21 and 22 are indented,
which suggests they are on the spur
circuit off Device 20.
10:15 Mon 15/02/10
Loop status
Current status :
Started
Total devices
:
127
Wiring status
:
Complete
Select
Last device found at address : 127
Loop status
Current status :
Started
Total devices
:
127
Wiring status
:
Complete
Select
Last device found at address : 127
Loop Map
9
1+
Device
1
Select
9
2
Device
2
9
3
Device
3
9
4
Device
4
Select
9
Device 1
|
9
Device 20
9
Device 21
9
Device 22
9
Device 23
Sounder
Disablement
Disablement
[amber LED]
[amber LED]
Nano panel based system
Back
The current loop status is 'Started'
The total number of devices found on the loop
The loop wiring status is complete
Back
The device number of the last device found
on the loop circuit
Back
10:15 Mon 15/02/10
The current loop status is 'Started'
The total number of devices found on the loop
The loop wiring status is complete
Back
The device number of the last device found
on the loop circuit
10:15 Mon 15/02/10
DEVICE
Select
Quit
Select a device from the range 1 to 127
10:15 Mon 15/02/10
Device : [
1]
Label
: Device 1
2
Type
: O H Sensor Sounder Strobe
Status : [ ENABLED ]
Assigned to Zone 1
Save
Quit
Scroll to 'Status'
at A3 or
'ENABLED' (factory default setting)
or 'DISABLED' the device
A4 only
To scroll range
Save
To move to
the next setting
25