Condition Codes For S-Quad Sensors - Honeywell GENT Nano panel-based Commissioning Instructions

Fire detection and alarm system
Table of Contents

Advertisement

Commissioning instructions

Condition Codes for S-Quad Sensors

Gen
Pos.
type
No.
Description
CC0
Optical subfire
E
N
V
CC1
Heat subfire
I
O
R
CC2
Gas subfire
N
M
E
CC3
N
T
CC4
Optical/Gas channel drift or out of
range
S
CC5
Heat channel drift or out of range
E
N
S
CC6
Optical/Gas channel noisy
O
(High freq)
R
CC7
Heat channel noisy (High
frequency)
D
CC8
Device firmware
E
V
I
CC9
Device transmission
C
E
54
Normal
band
0
1
None
Small signal sensed
[Check location, state & type]
None
Small signal sensed
[Check location, state & type]
-
Small signal sensed
[Check location, state & type]
-
OK
OK
OK
Single HF noise event
detected
OK
Single HF noise event
detected
OK
Isolated fault
[Note/report]
OK
Low error rate
Condition codes
Sub fault band
2
Subfire
[Check location, state & type]
Subfire
[Check location, state & type]
Subfire
[Check location, state & type]
Close to acceptable limit
Multiple HF noise seen
(Check location and report)
Multiple HF noise seen
(check location and report)
Repetitive fault
[Note / report / replace]
Medium error rate
[Report]
Fault band
3
Out of limits
[Clean/replace]
Out of limits
[Clean/replace]
Total failure
[Replace]
High error rate
[Replace]
4188-949 issue 3_05/10_Nano Comms inst.