Difference Between Nano Panel At V1.00 And V1.3X; Zoning Devices; Feature Changes; New Features - Honeywell GENT Nano panel-based Commissioning Instructions

Fire detection and alarm system
Table of Contents

Advertisement

Difference between Nano panel at V1.00 and V1.3x

The differences between Nano panel with Main Controller at V1.00 and V1.3x are such that V1.3x covers the requirements of EN54 Part 2.

Zoning devices

A Nano panel having Main Controller at V1.3x will have all the detection devices in zones, with all other devices not zoned. For example:
The following devices can be placed in a Zone:
¨
All S-Quad Sensors
¨
Manual Call Point
¨
Beam Receiver
¨
Keyswitch Interface
¨
Single Input Interface

Feature changes

Features
V1.00
Zoned devices
All devices zoned
Loop Maps
Just label shown
Channel Fires
Fire raised in Device Zone
External Evacuate
Evacuates/Silences All sectors including PLANT
Test Fires
Uses zone immediate C&E

New features

¨
Fast find device, see page 26
¨
One man commission mode, see page 62
¨
Directly control sectors from sector status form, see page 63.
¨
Option for new fire to resound alarms, see page 58
¨
Interface pulse widths can be set for each signal, see page 59.
4188-949 issue 3_05/10_Nano Comms inst.
The following devices cannot be zoned.
¨
All S-Cubed
¨
Beam Transmitter
¨
Single LV Output Interface
¨
Single MV Output Interface
¨
4 Channel LV Interface
¨
Mains Powered Interface
V1.3X
Only S-Quad, MCP, Beam Rx and Interface Inputs Zoned
Label, spur level identification, SAFE address identification and condition codes shown
Fire raised in Channel Zone
Behaves exactly as Sound/Silence Alarms buttons. This includes the action of Master Alarms and Fire
relay if configured
Evacuate all enabled ALARM sectors
"
The channels on a Mains Powered Interface unit and a 4-channel LV
Interface unit will have an associated zone regardless of whether they are
inputs or outputs.
Nano panel based system
35