How To Change The 'Signal' Settings; How To Set Up Weekly 'Fire Test Reminder - Honeywell GENT Nano panel-based Commissioning Instructions

Fire detection and alarm system
Table of Contents

Advertisement

How to change the 'Signal' Settings

The tone style and Interface output pulse settings of Evacuate, Alert and Class Change signals can be changed from factory default settings. You will need to be at access level 3 or above to make
changes to signal settings.
Menu
Select
Settings
After making changes to this form you will need to back-up the data to
memory. Ensure the write protect link P9 on the MCB is configured in
the ENABLED position to allow back-up of data.

How to set up weekly 'Fire test reminder'

A fire test reminder message can be configured to appear on the display on a specified day of the week to remind 'responsible person' to conduct a weekly fire test on the system. The message is
displayed at the beginning of the reminder day and is automatically removed the next day. You will need to be at access level 3 or above to set up a weekly fire test reminder.
Menu
Select
User
System
4188-949 issue 3_05/10_Nano Comms inst.
Select
Alarms
>
Signals
Select
Weekly Test >
>
Signal Settings
Tone Style
Test
: [½ SECOND PULSE
C.Change
: [CONTINUOUS
Select
Alert
: [1/4 SECOND PULSE]
Evacuate
: [NEE/NAW
Save
The factory default settings for interface outputs are shown
here. To change the settings select from a range 0 to 15.
0 - OFF
4 - 160ms
8 - 630ms
1 - 10ms
5 - 250ms
9 - 800ms
2 - 40ms
6 - 350ms
10- 980ms
3 - 90ms
7 - 480ms
11- 1.2s
Select
Select
Settings
Nano panel based system
The '1/4 SECOND PULSE' tone style is referred to as 'Intermittent'
in the Nano Commissioning tool, they mean the same.
1/2 SECOND PULSE (Factory default
setting), 1 SECOND PULSE 1/4 SECOND
PULSE, NEE-NAW or CONTINUOUS.
CONTINUOUS (Factory default setting),
1/2 SECOND PULSE, 1 SECOND PULSE
10:15 Mon 16/02/09
1/4 SECOND PULSE or NEE-NAW
I/O Pulse
1/4 SECOND PULSE(Factory default
]
[ 10]
setting), NEE-NAW, CONTINUOUS,
]
[ 15]
1/2 SECOND PULSE or 1 SECOND PULSE
[ 10]
]
[ 15]
NEE-NAW
(Factory default setting)
Quit
CONTINUOUS, 1/2 SECOND PULSE,
1 SECOND PULSE OR 1/4 SECOND PULSE
Save
12- 1.4s
13- 1.6s
14- 1.9s
15- ON
To scroll the
range
10:15 Tue 16/02/10
Weekly Fire Test Settings
Reminder is :
[OFF]
Test Day is :
[MONDAY
]
Prompt: WEEKLY FIRE TEST DUE TODAY
Save
Quit
Set Weekly fire test reminder to 'ON'
Select a test day from 'MONDAY' to 'SUNDAY'
or 'OFF' (factory default setting)
To scroll the
To move to
the next setting
range
To move to
next setting
Save
59