System Messages
Number
290042
An attempt was made to execute several
downloads/memory functions
simultaneously.
The last action was not executed.
290050
Acknowledgement that the exportation of
data records has started.
290051
Acknowledgement that the exportation of
data records has been completed
successfully.
290052
Acknowledgement that the exportation of
data records has been terminated due to
errors.
290053
Acknowledgement that the importation of
data records has been started.
290054
Acknowledgement that the importation of
data records has been completed
successfully.
290055
Acknowledgement that the importation of
data records has been terminated due to
errors.
290056
The value in the specified line/column could
not be read/written without errors.
The action was canceled.
300000
Process monitoring (e.g. with PDiag or
S7-Graph) has been programmed incorrectly.
More messages are displayed
simultaneously than specified in the technical
data related to the CPU. The CPU cannot
manage subsequent Alarm_S messages
and transfer them to the operating units.
310000
An attempt is being made to print too many
protocols simultaneously.
Since only one protocol can be printed at a
time, the print job is rejected.
310001
An error occurred on triggering the printer.
The protocol is either not printed or printed
with errors.
1)
The optional parameter %1 at the start of the message may contain an identification for the S7 connection
when several S7s are in parallel operation and are connected to diagnostics equipment.
2)
A WinCC channel provides the message texts via an interface. This text is issued via this message.
ProTool/Pro RT has no influence on this text.
3)
The specified text comes from the component resources.
C-18
CuuDuongThanCong.com
Effect/Cause
Remedy
Trigger the function again after waiting a
short period.
Ensure that the structure of the data records
on the data medium and the current recipe
structure on the operating unit are identical.
Ensure that the structure of the data records
on the data medium and the current recipe
structure on the operating unit are identical.
Check the specified line/column.
Modify the configuration in the CPU.
Wait until printout of the last active protocol
has been concluded.
Repeat the print job, if necessary.
Evaluate the additional system message,
related to this message, which is also issued.
Repeat the print job, if necessary.
TP 170A Equipment Manual