System Messages
Number
200002
Coordination is not executed at present
because the address format of the area
pointer does not match the internal storage
format.
200003
Coordination can be executed again
because the last error status has been
eliminated (return to normal operation).
200004
It is possible that coordination is not
executed.
200005
No more data is read or written.
This can have various causes:
The cable is defective.
The PLC does not respond, is defective,
etc.
The system is overloaded.
210000
Jobs are not processed because the
address configured in the PLC does not
exist/has not been set up.
210001
Jobs are not processed because the
address configured in the PLC cannot be
written to/read from.
210002
Jobs are not executed because the address
format of the area pointer does not match the
internal storage format.
210003
The job mailbox is processed again because
the last error status has been eliminated
(return to normal operation).
210004
It is possible that the job mailbox is not
processed.
210005
A PLC job was triggered by an impermissible
number.
210006
A fault occurred while attempting to execute
the PLC job. The PLC job is, therefore, not
executed.
Observe the subsequent/previous system
message, if appropriate.
2)
220000
See footnote
220001
The tag is not downloaded because the
associated channel/the unit does not support
downloading the data type bool/bit.
220002
The tag is not downloaded because the
associated channel/the unit does not support
downloading the data type byte.
220003
The associated driver could not be uploaded.
It is possible that the driver is not installed.
C-12
CuuDuongThanCong.com
Effect/Cause
Remedy
– (Internal error)
Check that the cable is connected and the
PLC is in order.
Reboot the system if the system message is
displayed continuously.
Change the address or set up the address in
the PLC.
Change the address or set up the address in
the PLC in an area which can be written
to/read from.
– (Internal error)
Check the PLC program.
Check the parameter types in the PLC job.
Compile the configuration again.
See footnote
Change the configuration.
Change the configuration.
Install the driver by re-installing ProTool/Pro
RT.
TP 170A Equipment Manual
https://fb.com/tailieudientucntt
Release 12/99

Hide quick links: