Siemens SIMATIC HMI TP 170A Equipment Manual page 79

Table of Contents

Advertisement

Number
150000
No more data is read or written.
This can have various causes:
The cable is defective.
The PLC does not respond, is defective,
etc.
Connection made to the wrong interface.
The system is overloaded.
150001
Connection is re-established because the
cause of the interruption has been
eliminated.
160000
No more data is read or written.
This can have various causes:
The cable is defective.
The PLC does not respond, is defective,
etc.
Connection made to the wrong interface.
The system is overloaded.
160001
Connection is re-established because the
cause of the interruption has been
eliminated.
160010
There is no connection to the server
because the server identification (CLS-ID)
cannot be established.
Values cannot be read or written.
160011
There is no connection to the server
because the server identification (CLS-ID)
cannot be established.
Values cannot be read or written.
160012
There is no connection to the server
because the server identification (CLS-ID)
cannot be established.
Values cannot be read or written.
1)
170000
S7 diagnostics messages are not displayed
because it is not possible to logon to the S7
diagnostics with this unit. The service
program is not supported.
1)
170001
The S7 diagnostics buffer cannot be
displayed because communication with the
PLC has been switched off.
1)
170002
The S7 diagnostics buffer cannot be
displayed because reading in the diagnostics
buffer (SZL) was terminated due to an error.
TP 170A Equipment Manual
Release 12/99
CuuDuongThanCong.com
Effect/Cause
System Messages
Remedy
Check that the cable is plugged in, the PLC
is operational, the correct interface is used.
Reboot the system if the system message is
displayed continuously.
Check that the cable is plugged in, the PLC
is operational, the correct interface is used.
Reboot the system if the system message is
displayed continuously.
Check the access rights.
Check, for example, whether:
the server name is correct
the computer name is correct
the server is registered
Check, for example, whether:
the server name is correct
the computer name is correct
the server is registered
Information for experienced users:
Interpret the value from HRESULT.
Switch the PLC online