System Messages
Number
1)
170003
The display of an S7 diagnostics message is
not possible. An internal error %2 has been
reported.
1)
170004
The display of an S7 diagnostics message is
not possible. An internal error with error class
%2, error number %3 has been reported.
1)
170007
It is not possible to read in the S7 diagnostics
buffer (SZL) because it was terminated with
an internal error with error class %2 and error
code %3.
180000
A component/OCX receives configuration
data with a version identification which is not
supported.
180001
The system is overloaded because too many
actions have been activated simultaneously.
Not all the actions can be executed, some
are rejected.
190000
It is possible that the tag will not be updated.
190001
The tag is updated following an error status
after the cause of the last error state has
been eliminated (return to normal operation).
190002
The tag is not updated because
communication to the PLC has been
switched off.
190004
The tag is not updated because the
configured address is not available for this
tag .
190005
The tag is not updated because the
configured PLC type does not exist for this
tag .
190006
The tag is not updated because it is not
possible to map the PLC type in the tag type.
190007
The tag values are not modified because the
connection to the PLC has been terminated
or the tag is offline.
190008
The threshold values configured for the tag
have been violated, e.g. by
an entered value,
a function,
a script.
190009
An attempt has been made to assign a value
to a tag which is outside the value range
permitted for this type.
E.g. a value of 260 entered for a byte tag or
a value of -3 for a signless word tag
C-10
CuuDuongThanCong.com
Effect/Cause
Remedy
Install a newer component.
Increase the configured cycle times or
basic clock.
Generate the messages slower (polling).
Trigger the scripts and functions at
greater intervals.
If the message appears more frequently:
Restart the operating unit.
Switch on communication via the function
"Set Online".
Check the configuration.
Check the configuration.
Check the configuration.
Switch Online or re-establish connection to
the PLC.
Observe the configured or current threshold
value of the tag.
Observe the value range for the tag type.
TP 170A Equipment Manual