Siemens SIMATIC HMI TP 170A Equipment Manual page 77

Table of Contents

Advertisement

Number
130002
The action was not executed.
140000
Online connection to the PLC has been
successfully established.
140001
Online connection to the PLC has been
disconnected.
140003
No tag updating or writing is executed.
140004
No tag updating or writing is executed
because the access point or the subrack
configuration is incorrect.
140005
No tag updating or writing is executed
because the address of the operating unit is
incorrect (possibly too high).
140006
No tag updating or writing is executed
because the baud rate is incorrect.
140007
No tag updating or writing is executed
because the bus profile is incorrect
(see %1).
The following parameters could not be
entered in the registry:
1:
Tslot
2:
Tqui
3:
Tset
4:
MinTsdr
5:
MaxTsdr
6:
Trdy
7:
Tid1
8:
Tid2
9:
Gap Factor
10: Retry Limit
TP 170A Equipment Manual
Release 12/99
CuuDuongThanCong.com
Effect/Cause
System Messages
Remedy
Close other applications.
Delete files no longer required from the hard
disk.
Check the connection and whether the PLC
is switched on.
Check the parameter definitions in the
Control Panel using "Set PU/PC interface".
Restart the system.
Check the connection and whether the PLC
is switched on.
Check the access point or the subrack
configuration (MPI, PPI, PROFIBUS) in the
Control Panel with "Set PU/PC interface".
Restart the system.
Use a different operating unit address.
Check the connection and whether the PLC
is switched on.
Check the parameter definitions in the
Control Panel using "Set PU/PC interface".
Restart the system.
Select a different baud rate in ProTool/Pro
(according to subrack, profile,
communication peer, etc.).
Check the user defined bus profile.
Check the connection and whether the PLC
is switched on.
Check the parameter definitions in the
Control Panel using "Set PU/PC interface".
Restart the system.