System Messages
Number
140008
No tag updating or writing is executed
because the configuration data is incorrect:
The following parameters could not be
entered in the registry:
0:
General errors
1:
Incorrect version
2:
Profile cannot be entered in the registry.
3:
Sub-network type cannot be entered in
the registry.
4:
Target rotation time cannot be entered
in the registry.
5:
Highest address (HSA) incorrect.
140009
No tag updating or writing is executed
because the module for the S7
communication was not found.
140010
No S7 communication peer could be found
because the PLC is switched off.
DP/T:
The option "Is not active as the only master"
is set in the Control Panel under "Set PU/PC
interface".
140011
No tag updating or writing is executed
because communication is interrupted.
140012
There is an initialization problem (e.g. when
ProTool/Pro RT has been terminated in the
Task Manager).
Or: another application (e.g. STEP7, WINCC)
is active with different bus parameters and
the driver cannot be started with the new bus
parameters (e.g. baud rate).
140013
The MPI cable is not plugged in and, thus,
there is no power supply.
140014
140015
Incorrect baud rate
Or: incorrect bus parameter (e.g. HSA)
Or: OP address HSA
Or: incorrect interrupt vector (interrupt does
not arrive at the driver)
140016
140017
C-8
CuuDuongThanCong.com
Effect/Cause
Remedy
Check the connection and whether the PLC
is switched on.
Check the parameter definitions in the
Control Panel using "Set PU/PC interface".
Restart the system.
Re-install the module in the Control Panel
using "Set PU/PC interface".
Switch the PLC on.
DP/T:
If only one master is connected to the
network, deactivate the option "Is not active
as the only master" in "Set PU/PC interface".
If the network has more than one master,
switch this master on. Do not modify any
settings here, otherwise a bus fault may
occur.
Check the connection and that the
communication peer is switched on.
Restart the operating unit.
Or start ProTool/Pro RT first and then the
other applications.
Check the connections.
Modify the operating unit address in the
configuration in PLC .
Correct the incorrect parameters.
Change the interrupt number.
Change the interrupt number.
TP 170A Equipment Manual
https://fb.com/tailieudientucntt
Release 12/99