System Messages
The message category enables the identification of a general area in which the
cause of the fault is to be found.
Note
System messages are issued in the language currently set on the operating unit.
System message parameters
The system messages may contain parameters which are not decoded for the user
but which are relevant in respect of the cause of an error since they provide a
reference to the source code from ProTool/Pro Runtime. These parameters are
issued according to the text "Error code:"
Number
10000
The print job could not be started or was
terminated for an unknown reason.
The printer is incorrectly configured.
Or: There are no rights for a network printer
available.
10001
No printer has been installed or no standard
printer configured.
10002
The intermediate buffer for printing graphics
is full. Up to two graphics can be buffered.
10003
Graphics can be buffered again.
10004
The intermediate buffer for printing lines in
text mode (e.g. messages) is full. Up to 1000
lines can be buffered.
10005
Lines of text can be buffered again.
10006
The Windows print system reports an error.
For information on the cause, refer to the text
printed and, if available, the error number.
Printing is not performed or it is incorrect.
20010
A fault has occurred in the script line called in
from the specified script. Execution of the
script function was, therefore, terminated.
In this case, it is advisable to check any
previous system messages too.
20011
An error has occurred in a script called in by
the script specified. Execution of the script
function has, therefore, been terminated in
the subscript.
In this case, it is advisable to check any
previous system messages too.
20012
Inconsistent configuration data is present.
Therefore, the script could not be created.
C-2
CuuDuongThanCong.com
Effect/Cause
Remedy
Configure the printer again.
Initiate the assignment of rights for a network
printer.
Install a printer and/or mark one as standard
printer.
Do not issue print jobs so quickly in
succession.
Do not issue print jobs so quickly in
succession.
Repeat the action, if necessary.
Select the specified script line in the
configuration.
Check tags, whether the types used are
permissible.
Check Functions, whether the number and
types of parameter are correct.
Select the scripts from the configuration
which were directly or indirectly called in via
the specified script.
Check tags, whether the types used are
permissible.
Check Functions, whether the number and
types of parameter are correct.
Compile the configuration again.