SiUS091601EA
FTX18/24UVJU
1. Remove the front grille.
2. Remove the electrical box.
3. Remove the shield plate of the electrical box.
4. Cut the address setting jumper JA on the PCB.
5. Remove the cover of remote controller battery.
6. Cut the address setting jumper J4.
Indoor unit PCB
Caution
Replace the PCB if you cut a jumper unintentionally.
Jumpers are necessary for electronic circuit. Improper operation may occur if you cut any of them.
Caution
Replace the remote controller if you cut a jumper unintentionally.
Jumpers are necessary for electronic circuit. Improper operation may occur if you cut any of them.
FVXS Series
1. Remove the electrical wiring box.
2. Cut the address jumper (JA) on the printed circuit board.
3. Cut the address jumper (J4) in the remote controller.
4. Attach the electrical wiring box as they were.
5. Attach the front panel and the front grille as they were.
Indoor Unit PCB
Part 7 Trial Operation and Field Settings
JB
JA
JC
JA
Address
JA
EXIST
1
CUT
2
Side electrical
wiring box cover
Front electrical
wiring box cover
Wireless Remote Controller
ADDRESS
EXIST
CUT
Jumper (J4)
Do not cut the left jumper.
(R9665)
Wireless Remote Controller
Sensor
securing plate
Jumper (J4)
ADDRESS
EXIST
CUT
∗ Do not cut the left jumper.
R7000286
Field Settings for FTX, FVXS Series
1
2
1
2
R7000284
(R18416)
208